EasyManua.ls Logo

Siemens Sentron 7KN POWERCENTER 1000 - Application Examples; Connecting to Higher-Level Applications

Siemens Sentron 7KN POWERCENTER 1000
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
6.4 Modbus TCP connection
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01
75
Reg-
ister
Len
gth
Designation For-
mat
Value range Default Unit Ac-
cess
POC
1000
5ST3
COM
5SL6
COM
5SV6
COM
3NA
COM
2604
1
Switching the
trip violations
alarm on and
off
U16
0 = Off
1 = On
0
RW
-
x
x
x
-
2605
2
Trip counter
limit value
FP32
1 … 10000
30
RW
-
x
x
x
-
2621
1
Bluetooth re-
ceived signal
strength (RSSI)
S16
-127 ... 20
-127
dBm
R
x
-
-
-
-
2622
1
Radio received
signal strength
(RSSI)
S16
-127 ... 127
-127
dBm
R
-
x
x
x
x
2624
2
Number of
short-circuit
trips
FP32
R
-
-
x
x
-
2626
1
Closing and
opening the trip
violations short-
circuit
U16
0 = Off
1 = On
1
RW
-
-
x
x
-
2627
2
Short-circuit
trips limit value
FP32
1 … 50
3
RW
-
-
x
x
-
2629
4
Current system
time and syn-
chronization
status {uint32_t
system time,
uint32_t Synch.
Status}
U8[8]
R
x
-
-
-
-
2633
1
Used radio
station (11-26)
U16
0 ... 26
26
R
x
-
-
-
-

Table of Contents