Parameter assignment/Addressing
5.1 MODBUS RTU
PAC RS485
Manual, 02/2008, A5E02091800B-01
41
Offset Number of
registers
Name Unit Format Value range Access
50019 2 Zero point suppression
level (% rated current)
% float 0.0 ... 10.0 RW
50021 2 Demand Period Min. unsigned long 1 ... 60 RW
0 = No synchronization
1 = Synchronization
via bus
50023 2 Synchronization - unsigned long
2 = Synchronization
via the digital input
RW
Table 5-10 Settings parameter for the digital input
Offset Number of
registers
Name Unit Format Value range Access
0 = Status only
1 = Pulse input
2 = High tariff/low tariff
switch
50025 2 "Action" mode - unsigned long
3 = DEMAND
synchronization
RW
0 = Import kWh
1 = Export kWh
2 = Import kvarh
50029 2 "Pulse input" mode - unsigned long
3 = Export kvarh
RW
50031 2 Pulses per unit (pulses
per 1000 Wh / VARh)
- unsigned long 1 ... 999 RW
Table 5-11 Settings parameter for the digital output
Offset Number of
registers
Name Unit Format Value range Access
50033 2 Switching function
Assignment to a vector
group
- unsigned long 0 ... 99 RW
0 = Off
1 = Device on
2 = Remote output
3 = Direction of
rotation
4 = Limit violation
50035 2 "Action" mode - unsigned long
5 = Energy pulse
RW