PAC RS485
Manual, 02/2008, A5E02091800B-01
75
Application examples
12
12.1 Examples of MODBUS communication
General information
The master makes a request to the slave, the SENTRON PAC Power Monitoring Device.
This replies to the master and confirms that it has executed the request.
Below is a representation of communication between the master and the slave using some
application examples from the "Application Log-File" of the bus master. The values are
specified in hexadecimal form.
Read measured values
Table 12-1 Request of the master
Address FC From register Number of registers to be read CRC
01 04 00 01 00 06 21 C8
Explanation:
From offset 0001:
voltage Va-n
Table 12-2 Response - confirmation of the slave
Address FC Number of read bytes Bytes CRC
01 04 0C 43 68 70 22
43 67 60 DC
43 67 9C A5
41 D7
Explanation:
12 232.4
231.4
231.6