Parameter assignment/Addressing
5.1 MODBUS RTU
PAC RS485
Manual, 02/2008, A5E02091800B-01
51
5.1.9 Modbus command parameters
Addressing the command parameters
You can use MODBUS function code 0x06 on the command parameters.
Table 5-20 Command parameters
Offset Number
of
registers
Name Unit Format Value range from ... to Access
60002 1 Reset maximum values - unsigned short 0 W
60003 1 Reset minimum values - unsigned short 0 W
0 = All
1 = Active Energy
Import Tariff 1
2 = Active Energy
Import Tariff 2
3 = Active Energy
Export Tariff 1
4 = Active Energy
Export Tariff 2
5 = Reactive Energy
Import Tariff 1
6 = Reactive Energy
Import Tariff 2
7 = Reactive Energy
Export Tariff 1
8 = Reactive Energy
Export Tariff 2
9 = Apparent
Energy Tariff 1
60004 1 Reset energy counter - unsigned short
10 = Apparent
Energy Tariff 2
W
60005 1 Synchronization of the
demand period
Min. unsigned short 1 ... 60 W
0 = High tariff 60006 1 Switching tariff - unsigned short
1 = Low tariff
W
60007 1 Acknowledge the diagnostics
bit
1)
(cf. stored bits in
unsigned long beginning
offset 205)
- unsigned short 0 ... ffffh W
0 = output 0 OFF 60008 1 Switching outputs
(if parameterized)
- unsigned short
1 = output 0 ON
W