Parameter assignment/Addressing
5.1 MODBUS RTU
PAC RS485
46 Manual, 02/2008, A5E02091800B-01
Offset Number of
registers
Name Unit Format Value range Access
0 = V_L1
1 = V_L2
2 = V_L3
3 = V_L12
4 = V_L23
5 = V_L31
6 = I_L1
7 = I_L2
8 = I_L3
9 = VA_L1
10 = VA_L2
11 = VA_L3
12 = P_L1
13 = P_L2
14 = P_L3
15 = VAR_L1
16 = VAR_L2
17 = VAR_L3
18 = PF_L1
19 = PF_L2
20 = PF_L3
21 = THDV_L1
22 = THDV_L2
23 = THDV_L3
24 = THDI_L1
25 = THDI_L2
26 = THDI_L3
27 = FREQ
28 = V_LN_AVG
29 = V_LL_AVG
30 = I_AVG
31 = VA_SUM
32 = P_SUM
33 = VAR_SUM
34 = PF_SUM
35 = V_BAL
50099 2 Source - unsigned long
36 = I_BAL
RW
50101 2 Value - float - RW
0 = greater than 50103 2 Modus ≥ / < - unsigned long
1 = less than
RW