Page #31 background imageLoading...
Page #31 background image
Expansion module I(N), I(Diff), analog
Manual, 04/2017, L1V30408520AG-01
31
Technical data
7
7.1 Technical specifications
Device configuration
I
N
- measuring input
I
5
- analog input
I
6
- analog input
Supply voltage
No external supply voltage is required. The expansion module is supplied via the PAC
device.
Measuring inputs
Connection to AC power systems is only possible via external current transformers.
I
N
input
Input current I
E
1 A / 5 A
Max. permissible continuous
current
1.2 A / 6 A
Current impulse overload
capability
100 A for 1 s
Zero point suppression level 1 mA
I
5
/ I
6
input
Input current I
E
20 mA
Max. permissible continuous
current
60 mA
Current impulse overload
capability
100 A for 1 s
Zero point suppression level 0.005 mA
Connection of external sen-
sors
0 / 4 ... 20 mA ( ≤ 50 V DC)
Refresh time ≤ 5 s

Other manuals for Siemens SENTRON Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SENTRON Series and is the answer not in the manual?

Siemens SENTRON Series Specifications

General IconGeneral
Product SeriesSENTRON
CategoryMeasuring Instruments
Frequency Range45-65Hz
Communication InterfacesModbus RTU, Ethernet
DisplayLCD
Protection ClassIP20
Operating Temperature Range-10°C to +55°C
Storage Temperature Range-25°C to +70°C