EasyManua.ls Logo

Siemens SIMATIC C7-613 - Page 133

Siemens SIMATIC C7-613
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
6-3
C7-613 Control System
A5E00138934-03
Uninstallation
Step Action
1 You do not need to take special measures to back up the user program of the
C7–613. It is saved as a non-volatile program on the MMC.
2 If you want to save the event buffer, you must first store it in a
DB (EVENT_BUFFER) on the MMC (see Section 5.6.1).
3 Switch on the power supply.
4 Loosen the cables from the shielding terminals and remove all connectors.
5 Remove the MMC.
6 Loosen the supports with a screw driver and remove the device from the control
panel.
7 Remove the labeling strips from the device.
Installation
Step Action
1 With the labeling facing downward, insert the labeling strips into the slits of the
front panel (see Section 2.1).
2 Complete the mechanical installation as described in Section 2.2. Be sure to
observe the relevant notes.
3 Insert the MMC.
4 Insert the cables and press the bare cables into the shielding terminals, as
described in Section 2.6.
5 Switch on the power supply.
6 Perform a general reset of the C7-613.
7 Switch the C7-613 to the RUN mode.

Table of Contents

Related product manuals