Error Information for HMI FBs and System Messages
B-13
C7-613 Control System
A5E00138934-03
System Message RemedyCause
$ 016
Entry < lower limit value
The input value is less
than the lower limit value.
The original value is
retained.
Repeat the entry with a higher value.
$ 017
Value not permissible for
data type
The entered value does
not match the data format.
Reenter the value using a value that is
permissible for the data format.
Check the configuration data of the variables.
$ 018
CPU is in RUN mode!
The CPU is in RUN mode.
However, HMI functions
are not possible, since the
“HMI API” FB is not being
called.
Check your program. Ensure that the “FB HMI”
is called.
$ 019
Screen cannot be shown
The selected screen is a
standard screen.
Standard screens cannot
be selected by means of
the job interface or the
“HMI MENU” FB.
A special screen with the
selected name is not
available.
Check the number of the selected screen. The
permissible numbers for special screens are
found in Section 4.5.3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC C7-613 and is the answer not in the manual?

Siemens SIMATIC C7-613 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC C7-613
CategoryControl Systems
LanguageEnglish

Related product manuals