Technical speci󹪝cations
7
Technical speci󹪝cations 6DL2804-xxDxx / xxExx
6DL2804- xxDxx xxExx
Degree of protection 6DL2804-****0 and 6DL2804-****2: IP65
6DL2804-****1: IP66
Dimensions: W x H x D 650 x 450 x 230 950 x 450 x 230
Material Stainless steel: DIN 1.4404, plate thickness 1.5 mm
Weight [kg] 30 43
Cover seal Silicone foam
Cable entries for
Voltage 2 M32 Ex e
Bus 4 M20 Ex e
Signals M16
3 rows (xxx3x) 39 66
5 rows (xxx5x) 65 110
Signals M20
3 rows (xxx4x) 36 57
5 rows (xxx6x) 60 95
Equipotential bonding rail 3 x 10 mm Cu
Bonding terminals 0.75 to 35 mm² Ex e for equipotential bonding cable, 4 mm²
for shield connection
Grounding conductor connection M6 screw, at least 16mm² with cable lug
Rated voltage/current
1)
These values depend on the installed components.
Ambient temperature range
6DL2804-1xxxx with installation of ET200iSP -20°C to +xx°C
2)
6DL2804-1xxxx with installation and heating -40°C to +xx°C
2) 3)
6DL2804-2xxxx
with installation of ET200iSP and electro-pneumatic system
AirLine Ex Typ 8650
0°C to +xx°C
2)
Permissible humidity Max. 95%
1)
The actual electrical values depend on the electrical equipment installed. The manufacturer speci󹪝es the 󹪝nal values within
the framework of these limits.
2)
The speci󹪝ed permissible ambient temperature range is only applicable if the enclosure is installed horizontally. The max.
ambient temperature is de󹪝ned depending on the power dissipation of the installed components, and speci󹪝ed on the
nameplate.
Note that the ambient temperature of the total con󹪝guration must be checked again if further components are subsequently
󹪝tted.
3)
The temperature range of -40°C is only possible when a heater is installed (see also section "Using the I/O device with
temperatures up to -40°C").
Distributed I/O device 6DL2804-1xxxx & 6DL2804-2xxxx
Hardware Installation Manual, 11/2023, A5E42025214-AC 29

Other manuals for Siemens SIMATIC ET 200iSP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200iSP and is the answer not in the manual?

Siemens SIMATIC ET 200iSP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200iSP
CategoryI/O Systems
LanguageEnglish

Related product manuals