Parameters/address space
4.3 Substitute value behavior
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
Manual, 10/2018, A5E03915895-AH
33
Diagnostics (maintenance) undervoltage
Diagnostics (maintenance) undervoltage
Diagnostics (maintenance) undervoltage is triggered if the supply voltage falls below the
value 19.2 V DC. When the supply voltage then exceeds 20.4 V DC, the diagnostics alarm
is reported as outgoing.
Channel diagnostics (Page 43)
Substitute value behavior
Substitute value behavior
The respective output behaves according to its configured substitute value behavior:
● Zero current or zero voltage
● Output substitute value
● Keep last value
The substitute value behavior is triggered in the following cases:
● STOP controller
● Controller failure (connection interrupted)
● Parameter assignment phase during startup
● Deactivating the IO device
● Station stop
– Missing server module
– Insertion of invalid I/O modules
– At least one I/O module is installed on an incorrect BaseUnit
Note
Reducing a configuration
If you reduce the configuration of the ET
200SP distributed I/O system and download the
configuration to the CPU, the modules which are no longe
r configured but still present
retain their original substitute value behavior. This applies until the supply voltage is
switched off at the interface module.