Interrupts, error messages, diagnostics and system alarms
5.3 Alarms
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
46 Manual, 10/2018, A5E03915895-AH
USI structure = W#16#0007
Table 5- 12 USI structure = W#16#0007
Data block name
Content
Comment
Bytes
USI
W#16#0007 Manufacturer-specific diagnostics if operation is not possi-
ble with existing bus configuration
Result: Station stop
The I/O modules fail → substitute value behavior
The interface module continues to exchange data with
the IO controller
2
Followed by the slot for the I/O module:
Slot
W#16#0001 to
W#16#0040
Bit 8 to 15
1
Bit 0 to 7
1
If slot 0 is specified, check the width of the station configuration (maximum 1 m).
Followed by 2 reserved bytes:
Reserved
1
Reserved
1
5.3.4
Invalid configuration states of the ET 200SP on PROFINET IO
Invalid configuration states
The following invalid configuration states of the ET 200SP distributed I/O system lead to the
failure of the IO device or prevent data exchange:
Number of modules exceeds maximum configuration.
Faulty backplane bus (e.g. defective BaseUnit). ET 200SP backplane bus interruptions do
not trigger an interrupt.
At least one I/O module is plugged into a different BaseUnit as the one configured in the
parameters.
No server module.
Invalid or incorrectly configured BusAdapter.
Note
Removal of the server module will trigger a station stop. All I/O modules of the ET
200SP
distri
buted I/O system fail (substitute value behavior) but the interface module continues to
exchange data.
Revoking the station stop (by correcting the invalid configuration state) leads to a brief failure
of the ET 200SP distributed I/O system and automatic
restart.