Interrupts/diagnostic messages 
  6.3 Diagnostics alarms 
Technology module TM ECC 2xPWM ST (6FE1242-6TM10-0BB1) 
Manual, 04/2018, A5E42681298B-AA 
51 
The following diagnostics alarms can be signaled: 
Table 6- 1  Diagnostics alarms, their meaning and remedies 
An internal module error has occurred. 
No load voltage  11
H
  No supply voltage L+ of the technology mod-
ule 
•  Check BaseUnit type 
•  Check wiring of the supply voltage L+ 
on the BaseUnit 
External error  1A
H
  This error can be caused by:  
•  CP level not permitted 
The voltage value is not in the tolerance 
band specified in IEC61851. 
•  Impermissible resistance at the PP termi-
nal 
The resistance value in the connector of 
the charging cable does not correspond to 
the specified tolerance band. See 
(Page 41) paragraph "Plug Present signal 
PP0 and PP1". 
•  No feedback after locking 
The signal of the feedback input does not 
match the "Locked" state. 
•  No feedback after unlocking 
The signal of the feedback input does not 
match the "Unlocked" state. 
•  No feedback after contactor "On" or "Off" 
The signal of the feedback input does not 
match the contactor state. 
•  No feedback after ventilation "On" or "Off" 
The signal of the feedback input does not 
match the ventilation state. 
•  Check the wiring 
•  Replace defective components 
Channel / compo-
nent temporarily 
unavailable 
1F
H
  Update of the firmware is being performed or 
has been canceled. The module does not 
read any process values in this state. 
•  Wait for firmware update 
•  Restart the firmware update 
Errors at digital 
outputs 
4
H
  This error can be caused by: 
•  Overload at outputs ACT0n, ACT0p, 
ACT1n, ACT1p 
•  Check process wiring