Climatic ambient conditions
The HMI device may be used under the following climatic ambient conditions:
Table 3-3 Climatic ambient conditions
Ambient conditions Permissible range Remarks
Temperature
Vertical mounting
Inclined mounting
from 0° C to 50° C
from 0 °C to 40 °C
See the "Mounting positions and type of
fixation" section
Relative humidity 10% to 90% Without condensation, corresponds to a
relative humidity, stress class 2
conforming to IEC 61131, part 2
Atmospheric pressure 1080 hPa to 795 hPa Corresponds to an elevation of -1000 to
2000 m
Pollutant concentration SO
2
: < 0.5 ppm;
relative humidity < 60%, no
condensation
H
2
S: < 0.1 ppm;
relative humidity < 60 %, no
condensation
Test: 10 ppm; 4 days
Test: 1 ppm; 4 days