EasyManua.ls Logo

Siemens SIMATIC HMI TP 177micro

Siemens SIMATIC HMI TP 177micro
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring the operating system
6.1 Configuring the operating system for the OP 73micro
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
79
6.1.3.5 Configure the data channel
Introduction
By disabling a data channel, you can protect the HMI device from unintentional overwriting of
project data and of the HMI device image.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Transfer Settings" was selected from the Loader menu.
Transfer Settings
Channel1: Serial
Figure 6-12 "Transfer Settings" menu
Procedure
1. Press
ENTER
.
The "Channel1: Serial" dialog opens.
Channel 1: serial
Value: Enable
Figure 6-13 "Channel1: Serial" dialog
This dialog is used to configure the RS495 port for serial data transfer.
1. Select the relevant setting using the
TAB
and
+/–
cursor keys.
"Disable"
Serial data transfer is disabled.
"Enable"
Serial data transfer is enabled.
2. Accept the required value with
ENTER
.
Note
Transfer settings
The data channel must be enabled to allow the download of project data from the
configuration computer to the HMI device.

Table of Contents

Related product manuals