Parameters
2.2 Parameter description
Interface module IM151-1 STANDARD (6ES7151-1AA06-0AB0)
Manual, 07/2015, A5E01075950-AD
13
Parameter description
2.2.1
41B
This parameter can be used to enable or disable ET 200S DPV1 operation. Data records
and interrupts (can be assigned parameters) are supported by class 1 and class 2 services
after DPV1 mode is enabled.
● The DP master must also support DPV1.
42B
≤ 1 m: The default setting for the maximum bus length is 1 m.
> 1 m: The bus length of the ET 200S is > 1 m and can be up to 2 m. However, this setting
will increase the response time of the ET 200S.
43B
Enable startup for set <> actual configuration
When this parameter is enabled:
● Removing and inserting modules during operation will not lead to an ET 200S station
failure
● If the actual configuration differs from the expected configuration, data exchange between
the ET 200S and the DP master will continue.
When this parameter is disabled:
● Removing and inserting modules during operation will lead to an ET 200S station failure.
● If the actual configuration differs from the expected configuration, data exchange between
the ET 200S and the DP master will cease.
Exception: Option handling
44B
Option handling in general
This parameter can be used as a general means of enabling or disabling option handling for
the entire ET 200S.
Assigning parameters for option handling with RESERVE modules (Page 20)