Configuring/Programming
10.1 Configuring CANopen Manager
SIMATIC PN/CAN LINK
112 Operating Instructions, 03/2022, A5E39895388-AC
The following consistency checks are performed between the columns during editing:
• Data type ↔ Min./Max. ↔ Initial value/New value
• Access ↔ PDO assignable
These changes are only local for the OD table until you press the "Apply and check data"
button. No other menu is affected.
Pressing the "Apply and check data" button initiates the following checks and updates:
1. A test is performed to see whether entries were added. These entries are then placed at the
correct location in the list. Only the newly added entries are taken into account during
sorting. You can only edit the "Index.Sub" field when you have added an entry. The field
remains editable until the entry is sorted in the table. After that, you can no longer change
the "Index.Sub" field. If you want to change it, you have to delete the entry and add it again.
2. A check is performed to determine whether the object can be read or written to so that data
exchange is possible.