Functions
5.2 CAN transparent
SIMATIC PN/CAN LINK
68 Operating Instructions, 03/2022, A5E39895388-AC
5.2.4 Control and status information
Control and status information
The following controller information is cyclically transmitted by the S7 controller to the
PN/CAN LINK:
Table 5- 8 Controller information in the PROFINET IO data (from S7 controller to PN/CAN LINK, 1
byte)
The CAN controller should be
"OFF".
The CAN controller should be
"ON".
The following status information is transmitted cyclically from the PN/CAN LINK to the S7
controller:
Table 5- 9 Status information in the PROFINET IO data (from PN/CAN LINK to S7 controller, 1 byte)
all data
Not all configured receive messages
have been received at least once
since the last transition to "ON".
All configured receive messages
have been received at least once
since the last transition to "ON".
controller
As specified by the S7
controller
1)
the specified threshold, or
PN/CAN LINK needs more than
2 seconds to synchronize itself
to the CAN bus.
As a consequence, the PN/CAN
LINK stops
transmitting/receiving packets.
1)
the specified threshold.
PN/CAN LINK still transmits /
1)
specified threshold.
This is the normal state.
1) The error counters customary in CAN and the associated thresholds are internal functions that are
not visible to the user.