SIMATIC PN/CAN LINK
156 Operating Instructions, 03/2022, A5E39895388-AC
Technical specifications
13
13.1 Technical specifications
Technical specifications PN/CAN LINK
Article number
6BK1620-0AA00-0AA0
General information
Product type designation
PN/CAN Link
Firmware version
FW update possible
Yes
Vendor identification (VendorID)
ID 03 00 00 53h acc. to CiA
Product function
I&M data
Yes; I&M0 to I&M3
Engineering with
STEP 7 TIA Portal configurable/integrated from version
STEP 7 V14 or higher
Installation type/mounting
Mounting
DIN rail, wall mounting, portrait mounting
Mounting position
any
Recommended mounting position
Horizontal
Rail mounting
Yes
Control cabinet installation
Yes
Supply voltage
Type of supply voltage
DC
Rated value (DC)
24 V
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Overvoltage protection
Yes
Short-circuit protection
Yes
Mains buffering
Mains/voltage failure stored energy time
10 ms
Input current
Current consumption (rated value)
0.09 A
Current consumption, max.
0.11 A
Power loss
Power loss, typ.
2.2 W
Interfaces
Interfaces/bus type
2x Ethernet (RJ45), 1x Sub-D (9-pin)
Supports protocol for PROFINET IO
automatic detection of transmission rate
No