Technical specifications
13.1 Technical specifications
SIMATIC PN/CAN LINK
Operating Instructions, 03/2022, A5E39895388-AC
157
Article number
6BK1620-0AA00-0AA0
Transmission rate, max.
100 Mbit/s
Number of RJ45 ports
2
Number of FC (FastConnect) connections
2
PROFINET functions
Assignment of the IP address, supported
Yes
Assignment of the device name, supported
Yes
1. Interface
Interface type
CAN according to CiA 303-1
Isolated
Yes; 500 V AC or 707 V DC
Interface types
Number of ports
1
Design of the connection
9-pin sub D socket
CAN
CAN operating modes
CAN Standard CAN 2.0A/B; CANopen Manager /
Slave acc. to CiA
Specification acc. to CiA
CiA 301 & CiA 302
Transmission rate, min.
50 kbit/s
Transmission rate, max.
1 000 kbit/s
Number of slaves, max.
126
Number of SDOs in parallel
16; Parallel
Number of PDOs
512; Send / receive
Services
Node/life-guarding
Yes
Heartbeat
Yes
SYNC
Yes
2. Interface
Interface type
PROFINET
Isolated
Yes; 1 500 V AC or 2 250 V DC
Interface types
RJ 45 (Ethernet)
Yes
Number of ports
2
integrated switch
Yes
Protocols
PROFINET IO Device
Yes
Interrupts/diagnostics/status information
Status indicator
Yes
Alarms
Yes
Diagnostics function
Yes