System overview
4.1 Field of application
SIMATIC PN/CAN LINK
Operating Instructions, 03/2022, A5E39895388-AC
27
General features
CAN interface according to ISO 11898-2 (High Speed CAN)
2 PROFINET interfaces (integrated switch) enable PROFINET line operation according to
Conformance Class B (CC-B).
In addition to the PROFINET and CAN protocol, the PN/CAN LINK also offers the CANopen
protocol. This means the PN/CAN LINK can be operated as a CANopen node and can also
take on the role of CANopen Manager in the CANopen network. The PN/CAN LINK can be
operated in the following three modes:
CANopen Manager
CANopen Slave
CAN transparent
The operating mode for the PN/CAN LINK is set via the associated HSP in the TIA Portal.
The PN/CAN LINK supports both the standard format (CAN 2.0A) as well as the extended
CAN format (CAN 2.0B).
The PN/CAN LINK can operate up to 126 nodes in the CAN network in Manager mode.
The CAN side supports baud rates from 50 kBaud up to 1000 kBaud.
The maximum permissible cable length of the CAN network is up to 1000 m (dependent
on data transmission rate, cable cross-section, number of nodes).