Functions
5.1 CANopen
SIMATIC PN/CAN LINK
60 Operating Instructions, 03/2022, A5E39895388-AC
Status information
The following status information is transmitted cyclically from the PN/CAN LINK to the S7
controller:
Table 5- 7 Structure of status information in the PROFINET IO data (from PN/CAN LINK to S7
controller, 1 byte)
acknowle
dgment
bit
The PN/CAN LINK is ready for reset.
A reset acknowledgment bit is used
in the data that are transmitted
cyclically from the PN/CAN LINK to
the S7 controller to provide
feedback to the S7 controller
regarding the reset of the CANopen
side. As soon as the command for
resetting the CANopen side has
been received, this bit is set to "1".
The S7 controller must then set the
reset bit to "0". When the reset of
the CANopen side is complete, the
PN/CAN sets the reset
acknowledgment bit to "0".
The PN/CAN LINK is currently
performing or has performed a reset
but the reset bit of the S7 controller is
LINK state
PN/CAN LINK state "Pre-Operational"
PN/CAN LINK state "Operational"
PN/CAN LINK state "Stopped"
status of
all data
There are receive OD entries whose
values have not yet been updated by a
corresponding PDO since the last
All receive OD entries have been
updated at least once by a PDO or SDO
since the last reset.