•
No load functions are running.
•
Testing with breakpoints is not used.
No SYNCUP is performed during testing with breakpoints. You will find more information
on testing with breakpoints in the STEP7 online help.
SYNCUP system state
Synchronization in the SYNCUP system state ensures that the two CPUs can operate
redundantly. With the SYNCUP system state, the redundant system switches from RUN-Solo
to the RUN-Redundant system state. Afterwards, both CPUs synchronously process the same
user program.
Starting SYNCUP
The initial situation is the RUN-Solo system state. The primary CPU of a redundant system is in
the RUN operating state and the backup CPU is in the STOP operating state.
The operating states are shown on the displays:
Table 11-4Starting SYNCUP
Primary CPU Backup CPU
6ES7 517-3HP00-0AB0
CPU 1517H-3 PN
X1: 192.168.0.1
X2: 192.168.1.1
[Primary] V3.0
RUN-Redundant
Overview
OK
6ES7 517-3HP00-0AB0
CPU 1517H-3 PN
X1: 192.168.0.2
X2: 192.168.1.1
[Backup] V3.0
STOP
Overview
OK
Start SYNCUP by:
•
Starting the backup CPU via the PG/PC/HMI device or the display, and the mode selector is
set to RUN.
or
•
Switching the mode selector on the backup CPU from STOP to RUN.
or
•
Powering on the backup CPU (mode selector to RUN).
271
Commissioning
11.4 Operating and system states
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD