Preparing the SYNCUP system state
After SYNCUP starts, the CPUs prepare SYNCUP:
The backup CPU switches to SYNCUP operating state and sends a status message to the
primary CPU.
The primary CPU then switches from the RUN operating state to RUN-Syncup.
The current operating states are shown on the displays:
Table 11-5Preparing SYNCUP
Primary CPU Backup CPU
6ES7 517-3HP00-0AB0
CPU 1517H-3 PN
X1: 192.168.0.1
X2: 192.168.1.1
[Primary] V3.0
RUN-Syncup
Overview
OK
6ES7 517-3HP00-0AB0
CPU 1517H-3 PN
X1: 192.168.0.1
X2: 192.168.1.1
[Backup] V3.0
SYNCUP
Overview
OK
Sequence of the SYNCUP system state
The operating systems of the two CPUs run through SYNCUP in five phases:
Copying the SIMATIC memory card
Restart of the backup CPU
Finishing tasks
Copying the work memory
Making up backup CPU lag
The display of the primary CPU shows you the current phase of the SYNCUP system state.
The display of the backup CPU shows "Connect..." state during the phases to until the
RUN-Redundant system state is reached.
272
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Commissioning
11.4 Operating and system states