ATEX approval
According to EN60079-15 (Electrical apparatus for potentially explosive atmospheres - Part
15: Type of protection "n") and EN 60079-0 (Electrical apparatus for potentially explosive gas
atmospheres - Part 0: General Requirements).
,,*([Q$,,&7*F
'(.5$$7(;;
OR
According to EN60079-7 (Electrical apparatus for potentially explosive atmospheres - Part 7:
Increased safety "e") and EN IEC 60079-0 (Electrical apparatus for potentially explosive gas
atmospheres - Part 0: General Requirements).
,,*([HF,,&7*F
'(.5$$7(;;
Special conditions in hazardous areas:
1.
The equipment shall only be used in an area of not more than pollution degree 2, as
defined in EN 60664-1.
2.
The equipment shall be installed in a suitable enclosure providing a degree of protection
not less than IP54 in accordance with EN60079-15 or EN60079-7. The ambient
conditions must be taken into consideration for use.
3.
Provisions shall be made to prevent the rated voltage from being exceeded by transient
disturbances of more than 119V.
UKEX approval
According to EN 60079-7 (Explosive atmospheres – Part 7: Equipment protection by
increased safety "e") and EN IEC 60079-0 (Explosive atmospheres – Part 0: Equipment -
General requirements).
II 3 G Ex ec IIC T4 Gc
DEKRA 21UKEX0008 X
Special conditions in explosive atmospheres:
1.
The equipment shall only be used in an area of not more than pollution degree 2, as
defined in EN60664-1.
2.
The equipment shall be installed in a suitable enclosure providing a degree of protection
not less than IP54 in accordance with EN IEC 60079-0. The ambient conditions must be
taken into consideration for use.
3.
Provisions shall be made to prevent the rated voltage from being exceeded by transient
disturbances of more than 119V.
355
Technical specifications
15.1 Standards and Approvals
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD