EasyManua.ls Logo

Siemens SIMOCODE pro

Siemens SIMOCODE pro
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Planning/Configuring
6.2 Configuring the DM-F LOCAL
40
SIMOCODE pro - Fail-Safe Digital Modules
Manual, 11/2017, NEB631679702000/RS-AA/002
6.2
Configuring the DM-F LOCAL
Note
The safety
-related functions can only be configured using the DIP switches.
Table 6- 1 Factory setting
OFF
Schematic
DIP switch
No.
ON
Without cross-circuit detection
1
With cross-circuit detection
1 NC + 1 NO evaluation
2
2 NC evaluation
2 x 1-channel
3
1 x 2-channel
Debouncing time for sensor inputs ∼ 50 ms
4
Debouncing time for sensor inputs ∼ 10 ms
Sensor input automatic start
5
Sensor input monitored start
Cascading input automatic start
6
Cascading input monitored start
With start-up testing
7
Without start-up testing
Automatic starting after power failure (not
permissible in conjunction with start-up testing)
8 No automatic starting after power failure
No function
-
No function
No function - No function
DANGER
Automatic starting after power failure. Risk of death or serious injury.
In the case of automatic starting after a power failure, the enabling circuits are connected
without pressing the Start button.
The desired configuration of the DM-F Local can be stored in SIMOCODE pro using the
SIMOCODE ES software (e.g. for documentation purposes). The stored configuration is then
compared with the actually effective settings on the DM-F Local (i.e., the settings defined
with the DIP switches). If the stored configuration is not the same as the effective
configuration, the following status message appears: "DM-FL Configuration deviates".

Table of Contents

Other manuals for Siemens SIMOCODE pro

Related product manuals