EasyManua.ls Logo

Siemens SIMOTICS GP series - Terminal Board and Grounding; Terminal Boxes, End Shields, Grounding Conductors, Sheet Metal Fan Covers; Additional Connecting Terminals for Monitoring Equipment and Anti-Condensation Heating

Siemens SIMOTICS GP series
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
B.1 Tightening torques
Standard motors SH 63 ... 355
142 Operating Instructions, 12/2018, A5E38483075A
B.1.2 Terminal board and grounding
Table B- 2 Tightening torques for electrical connections on the terminal board and grounding
Thread ∅
M 3.5
M 4
M 5
M 6
M 8
M 10
M 12
M 16
Nm
min
0.8
0.8
1.8
2.7
5.5
9
14
27
Max.
1.2
1.2
2.5
4
8
13
20
40
B.1.3 Terminal boxes, end shields, grounding conductors, sheet metal fan covers
If no other tightening torques are specified, then the values in the following table apply.
Table B- 3 Tightening torques for screws on the terminal box, end shields, screw-type grounding conductor connections
Thread ∅
M 3.5
M 4
M 5
M 6
M 8
M 10
M 12
M 16
M20
Nm
min
0.8
2
3.5
6
16
28
46
110
225
max
1.2
3
5
9
24
42
70
165
340
Table B- 4 Tightening torques for self-tapping screws on the terminal box, end shields, screw-type grounding conductor
connections, sheet metal fan covers
Thread
M 4
M 5
M 6
Nm
min
4
7.5
12.5
max 5 9.5 15.5
B.1.4 Additional connecting terminals for monitoring equipment and anti-condensation
heating
Table B- 5 Tightening torques for monitoring equipment and anti-condensation heating
Main terminal box
EN 60999-1: 2000 table 4 III
0.4 Nm
Auxiliary terminal box
min 0.6 Nm
max 0.8 Nm

Table of Contents