Table 3- 1 Air cooling requirements for operation with rated power (LO)
Required cooling air flow
Frame
size
LO power rating
I/s CFM
FSA 0.37 kW ... 3.0 kW 7 14
FSB 4.0 kW ... 7.5 kW 9 19
FSC 11.0 kW ... 18.5 kW 20 40
FSD 22.0 kW ... 30.0 kW 55 120
FSE 37.0 kW ... 45.0 kW 110 240
FSF 55.0 kW ... 90 kW 150 320
Table 3- 2 Power losses of Power Module components in Watts (@ nominal voltage)
For Power Module
Power losses of … FSA FSB FSC FSD FSE FSF
Power Module 20 …
150
25 …
300
30 …
500
440 ... 720 1000 ...
1300
1500 ...
2500
Control Unit <40