4.9 EMC guidelines
Power Module PM230 IP55
56 Hardware Installation Manual, 2010-07-02, A5E02923635A AB
4.9.5 Inverter shielding in detail, FSA to FSC
The figure below shows the necessary shielding of the Power Module.
+LJKIUHTXHQF\
HTXLSRWHQWLDOERQGLQJ
6WDQGDUG3*JODQG
0RWRUFDEOHVKLHOG
&RQQHFWVKLHOGZLWKD
ODUJHFRQWDFHDUHD
/LQHVXSSO\FDEOH
XQVKLHOGHG
&ODPSXVHGDVFDEOH
JULS
Figure 4-9 Power Module shielding, FSA … FSC
If a terminal wiring of the Control Unit is required, a shielded cable has to be used. The cable
shield has to be connected to the gland plate via an electrically conductive PG gland.
This cable has to be fed through the left-hand hole of the gland plate, especially on frame
size C filter class B Power Modules.