EasyManua.ls Logo

Siemens SINAMICS G120P - Specifications; Input Current Operation; Table 6- 2 PM230 Frame Sizes A, 3 AC 380 V

Siemens SINAMICS G120P
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.3 Specifications
Power Module PM230 IP55
Hardware Installation Manual, 2010-07-02, A5E02923635A AB
75
6.3 Specifications
6.3.1 Input current operation
Note
The Power Module is only for operation at a maximum line impedance of 1% Vk. No line
reactor can be used with the Power Module.
NOTICE
UL-certified fuses must be used
In order that the system is in compliance with UL, UL certified fuses, circuit breakers or self-
protected combination motor controllers must be used.
Power Module specifications
Table 6- 2 PM230 Frame Sizes A, 3 AC 380 V … 480 V, ± 10%
Order No. Class A filter
Class B filter
6SL3223-0DE13-7AA0
6SL3223-0DE13-7BA0
6SL3223-0DE15-5AA0
6SL3223-0DE15-5BA0
6SL3223-0DE17-5AA0
6SL3223-0DE17-5BA0
Values based on Low Overload
● LO power
● LO input current
● LO Output current
0.37 kW
1.3 A
1.3 A
0.55 kW
1.8 A
1.7 A
0.75 kW
2.3 A
2.2 A
Values based on High Overload
● HO power
● HO input current
● HO output current
0.25 kW
0.9 A
0.9 A
0.37 kW
1.3 A
1.3 A
0.55 kW
1.8 A
1.7 A
Common values
● Power losses
● Fuse
● Required cooling air flow
● Cross section of line and
motor cable
● Tightening torque for line and
motor cable
● Weight
0.06 kW
10 A
7 l/s
1 … 2.5 mm
2
0.5 Nm
4.3 kg
0.06 kW
10 A
7 l/s
1 … 2.5 mm
2
0.5 Nm
4.3 kg
0.06 kW
10 A
7 l/s
1 … 2.5 mm
2
0.5 Nm
4.3 kg