Technical specifications
6.3 Specifications
Power Module PM230 IP55
78 Hardware Installation Manual, 2010-07-02, A5E02923635A AB
Table 6- 7 PM230 Frame Sizes D, 3 AC 380 V … 480 V, ± 10%
Order No. Class A filter
Class B filter
6SL3223-0DE32-2AA0
6SL3223-0DE32-2BA0
6SL3223-0DE33-0AA0
6SL3223-0DE33-0BA0
Values based on Low Overload
● LO power
● LO input current
● LO Output current
22 kW
42 A
45 A
30 kW
56 A
60 A
Values based on High Overload
● HO power
● HO input current
● HO output current
18,5 kW
36 A
38 A
22 kW
42 A
45 A
Common values
● Power losses
● Fuse
● Required cooling air flow
● Cross section of line and
motor cable
● Tightening torque for line and
motor cable
● Weight
0.52 kW
63 A
39 l/s
16 … 35 mm
2
6 Nm
30,2 kg
0.68 kW
80 A
39 l/s
16 … 35 mm
2
6 Nm
30,2 kg
Table 6- 8 Frame Sizes E, 3 AC 380 V … 480 V, ± 10%
Order No. Class A filter
Class B filter
6SL3223-0DE33-7AA0
6SL3223-0DE33-7BA0
6SL3223-0DE34-5AA0
6SL3223-0DE34-5BA0
Values based on Low Overload
● LO power
● LO input current
● LO Output current
37 kW
70 A
75 A
45 kW
84 A
90 A
Values based on High Overload
● HO power
● HO input current
● HO output current
30 kW
56 A
60 A
37 kW
70 A
75 A
Common values
● Power losses
● Fuse
● Required cooling air flow
● Cross section of line and
motor cable
● Tightening torque for line and
motor cable
● Weight
0,99 kW
100 A
39 l/s
25 … 50 mm
2
6 Nm
35,8 kg
1,2 kW
125 A
39 l/s
25 … 50 mm
2
6 Nm
35,8 kg