EasyManua.ls Logo

Siemens SINAMICS G120P - Table 6- 3 PM230 Frame Sizes A, 3 AC 380 V; Table 6- 4 PM230 Frame Sizes A, 3 AC 380 V

Siemens SINAMICS G120P
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.3 Specifications
Power Module PM230 IP55
76 Hardware Installation Manual, 2010-07-02, A5E02923635A AB
Table 6- 3 PM230 Frame Sizes A, 3 AC 380 V … 480 V, ± 10%
Order No. Class A filter
Class B filter
6SL3223-0DE21-1AA0
6SL3223-0DE21-1BA0
6SL3223-0DE21-5AA0
6SL3223-0DE21-5BA0
6SL3223-0DE22-2AA0
6SL3223-0DE22-2BA0
Values based on Low Overload
● LO power
● LO input current
● LO Output current
1,1 kW
3,2 A
3,1 A
1,5 kW
4,2 A
4,1 A
2,2 kW
6,1 A
5,9 A
Values based on High Overload
● HO power
● HO input current
● HO output current
0,75 kW
2,3 A
2,2 A
1,1 kW
3,2 A
3,1 A
1,5 kW
4,2 A
4,1 A
Common values
● Power losses
● Fuse
● Required cooling air flow
● Cross section of line and
motor cable
● Tightening torque for line and
motor cable
● Weight
0,07 kW
10 A
7 l/s
1 … 2,5 mm
2
0,5 Nm
4,3 kg
0,08 kW
10 A
7 l/s
1 … 2,5 mm
2
0,5 Nm
4,3 kg
0,1 kW
10 A
7 l/s
1,5 … 2,5 mm
2
0,5 Nm
4,3 kg
Table 6- 4 PM230 Frame Sizes A, 3 AC 380 V … 480 V, ± 10%
Order No. Class A filter
Class B filter
6SL3223-0DE23-0AA0
6SL3223-0DE23-0BA0
Values based on Low Overload
● LO power
● LO input current
● LO Output current
3 kW
8,0 A
7,7 A
Values based on High Overload
● HO power
● HO input current
● HO output current
2,2 kW
6,1 A
5,9 A
Common values
● Power losses
● Fuse
● Required cooling air flow
● Cross section of line and
motor cable
● Tightening torque for line and
motor cable
● Weight
0,12 kW
10 A
7 l/s
1,5 … 2,5 mm
2
0,5 Nm
4,3 kg