EasyManua.ls Logo

Siemens SINAMICS SM120 - Page 39

Siemens SINAMICS SM120
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Technical data for 322 and 323:
Terminals 1-10:
Auxiliary voltage: 24 VDC
Max. total load current of +24 V auxiliary voltage of terminals X321, X322, and X323
combined: See note
Input voltage range: -3 to 30 V
Typical current consumption: 10 mA at 24 VDC
Input delay: For "0" to "1" max. 50 μs; for "1" to "0" max. 100 μs
Electrical isolation: Reference potential is terminal MEXT1 or MEXT2
Level (including ripple): High signal level: 15 to 30 V; low level: -3 to 5 V
Terminals 11-14:
The analog inputs can be toggled between current and voltage input using switches S5.0,
S5.1, S6.0, and S6.1.
Voltage: 0 to 10 V; Ri > 100 kOhm; resolution 12-bit
Current: 0 to 20 mA; Ri = 250 Ohm; resolution 11-bit
Note
Maximum load current from the 24 VDC auxiliary voltage and the digital outputs
The total load current via terminals 2 and 9 at X321 and 2, 3, 6, and 7 at X322 and X323 of
the 24 VDC auxiliary voltage, together with the digital outputs, is protected by an internal 4 A
fuse. A continuous current of 3 A in total through this fuse must not be exceeded. In your
application, dimension the total load currents from the eight digital outputs and the terminals
of the 24 VDC auxiliary voltage accordingly.
Note
Open digital input
An open input is interpreted as "low".
Connect the MEXT1 or MEXT2 terminals to enable the digital inputs to work. The following
possibilities exist:
The incorporated ground reference of the digital inputs
A jumper to terminal M
In this case, the isolation for these digital inputs is removed.
Note
Diagnostics when the 24 VDC auxiliary voltage fuse ruptures
The 24 VDC auxiliary voltage is protected internally by a 4 A fuse. A ruptured fuse is indicated
by loss of the auxiliary power and/or by a diagnostic message. All digital outputs are also
affected by a ruptured fuse. The user cannot replace this fuse. Replace the component and
send it for repair.
Description
3.4 Components
SINAMICS SM120 6SL38855?B
Operating Instructions 12/2015 39

Table of Contents

Other manuals for Siemens SINAMICS SM120