I/O interfacing
Create a low-impedance ground connection for additional cabinets, system components,
and distributed devices with the largest possible cross-section (at least 16 mm²).
Ground unused lines at one end in the cabinet.
Choose the greatest possible clearance between the power and signal cables (at least 20
cm). The greater the distance over which the cables are routed in parallel, the greater the
clearance must be. You must install additional shields if sufficient clearance cannot be
maintained.
Avoid unnecessarily long cable loops.
The operating coils for contactors and relays in the drive must be connected to overvoltage
limiters (e.g. RC elements or varistors).
In order to reduce noise/interference entering or exiting via the cable, filter auxiliary voltages
in the control cabinet.
6.3 Potential concept
A noise-free connection between the internal and external supply voltage can be achieved by
connecting the 0 V potentials to each other and grounding them. This also eliminates the need
for the control circuit insulation monitor required by DIN EN 60204-1.
,QWHUQDO
ORDGV
([WHUQDO
ORDGV
3
0
3
0
1
Image 6-3 Potential concept
6.4 Cable cross-sections
Table 6-1 Cable cross-sections
Object Cross-section Remark
Power cable Max. 240 mm
2
max. 4 per terminal
Cabinet protective conductor Max. 120 mm² -
See also
Torques (Page 105)
Electrical connection
6.4 Cable cross-sections
SINAMICS SM120 6SL38855?B
78 Operating Instructions 12/2015