EasyManua.ls Logo

Siemens SINAMICS SM120 - Page 90

Siemens SINAMICS SM120
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LED Color Status Description; cause Remedy
RUN /
ERR
- Off The electronic power supply is missing
or lies outside the permissible tolerance
range.
-
Green Continuous
light
The component is ready for operation
and cyclic DRIVE-CLiQ communication
is in progress.
-
Orange Continuous
light
DRIVE-CLiQ communication is being es‐
tablished.
-
Red Continuous
light
At least one fault is present in the com‐
ponent.
LED is controlled irrespective of the cor‐
responding messages being reconfig‐
ured.
Remedy and acknowledge fault.
Green/red 0.5 Hz flashing
light
Firmware download in progress. -
2 Hz flashing
light
Firmware download is complete. Waiting
for POWER ON.
Carry out a POWER ON.
Green/or‐
ange
or
Red/orange
Flashing light Component recognition via LED is acti‐
vated.
The color depends on the LED state
when component recognition is activated.
-
Operation
8.3 Fault and system messages
SINAMICS SM120 6SL38855?B
90 Operating Instructions 12/2015