Safety Integrated
9.5 Commissioning extended functions
Getting Started - SINAMICS Startdrive
76 Getting Started, 01/2015
3. You must enable the associated SLS safety function. Select "Enable" in the selection list
in front of the required safety function. The other safety functions also enabled but not
deployed are deactivated later in the safety program.
Figure 9-11 Extended functions: Enable PROFIsafe control type and safety function
4. Click "SLS" in the secondary navigation.