Parameter number:
945 dec → p0945 (fault code) is read.
Subindex:
0 dec → Reading starts at index 0.
Initiate parameter request.
If ZSW1.3 = "1" → Initiate parameter request
Evaluate the parameter response.
Parameter response Offset
Response header Request reference mirrored =
25 hex
Response ID = 01 hex 0 + 1
Axis mirrored = 02 hex Number of parameters = 01 hex 2 + 3
Parameter value Format = 06 hex Number of values = 08 hex 4 + 5
1st value = 1355 dec 6
2nd value = 0 dec 8
... ...
8th value = 0 dec 20
Information about the parameter response:
Request reference mirrored:
This response belongs to the request with request reference 25.
Response ID:
01 hex → Read request positive, values stored as of 1st value.
Axis mirrored, number of parameters:
The values correspond to the values from the request.
Format:
06 hex → Parameter values are in the unsigned16 format.
Number of values:
08 hex → Eight parameter values are available.
1st value ... 8th value
A fault is only entered in value 1 of the fault buffer for drive 2.
Example 2: Writing parameters (multi-parameter request)
Requirements
The PROFIdrive controller has been commissioned and is fully operational.
PROFIdrive communication between the controller and the device is operational.
Communication
A.1 Communication
Industrial Security
102 Configuration Manual, 08/2017, A5E36912609A