EasyManua.ls Logo

Siemens SINAMICS - Page 201

Siemens SINAMICS
236 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table A-47 Class Attribute
No. Service Type Name
1 get UINT16 Revision
2 get UINT16 Max Instance
3 get UINT16 Num of Instances
Parameter access to drive object 0 (DO 0) is realized via this class.
Example: Read parameter 2050[10] (connector output to interconnect the PZD received from
the fieldbus controller)
Get Attribute single function with the following values:
● Class = 401 hex
● Instance = 2050 = 802 hex ≙ parameter number
● Attribute = 10 = A hex ≙ Index 10
Example: Parameter 1520[0] writing (upper torque limit)
Set Attribute single function with the following values:
● Class = 401 hex
● Instance = 1520 = 5F0 hex ≙ parameter number
● Attribute = 0 = 0 hex ≙ index 0
● Data = 500.0 (value)
Parameter Object, Instance Number: 401 hex ... 43E hex
Supported services
Class
● Get Attribute All
● Get Attribute Single
Instance
● Get Attribute Single
● Set Attribute Single
Table A-48 Class Attribute
No. Service Type Name
1 get UINT16 ‑
2 get UINT16 Max slot num
3 get UINT16 Max slot ID
Parameter access to drive object 0 (DO 0) is realized via this class.
The class structure is analog to 401 hex. Drive object (DO) is selected via the class number.
Example:
0x401 -> DO 1
0x402 -> DO 2
Communication
A.1 Communication
Industrial Security
Configuration Manual, 08/2017, A5E36912609A 201

Table of Contents