Significance Remark Additional
info
0x03 Invalid subindex. Access to a subindex that does not exist. Subindex
0x04 No array. Access with subindex to an unindexed parameter.
0x05 Wrong data type. Modification access with a value that does not match the data
type of the parameter.
0x06 Illegal set operation (only reset al‐
lowed).
Modification access with a value not equal to 0 in a case
where this is not allowed.
Subindex
0x07 Description element cannot be
changed.
Modification access to a description element that cannot be
changed.
Subindex
0x09 No description data available. Access to a description that does not exist (the parameter
value exists).
0x10 Read job will not be executed. The read request is refused because know-how protection is
active.
0x0B No operating priority. Modification access with no operating priority.
0x0F No text array exists. Access to a text array that does not exist (the parameter value
exists).
0x11 Request cannot be executed due to
operating status.
Access is temporarily not possible for unspecified reasons.
0x14 Illegal value. Modification access with a value that is within the limits but is
illegal for other permanent reasons (parameter with defined
individual values).
Subindex
0x15 Response too long. The length of the present response exceeds the maximum
transfer length.
0x16 Illegal parameter address. Illegal or unsupported value for attribute, number of elements,
parameter number, subindex or a combination of these.
0x17 Illegal format. Write request: Illegal or unsupported parameter data format.
0x18 Number of values inconsistent. Write request: A mismatch exists between the number of val‐
ues in the parameter data and the number of elements in the
parameter address.
0x19 Drive object does not exist. You have attempted to access a drive object that does not
exist.
0x20 Parameter text cannot be changed
0x21 Service not supported. Illegal or unknown request ID
0x65 Parameter presently deactivated. You have tried to access a parameter that, although available,
does not currently perform a function (e.g. n control set and
access to a V/f control parameter).
0x6B Write access for the enabled control‐
ler.
Write access is possible while the device is in the "Controller
enable" state.
Pay attention to the parameter attribute "changeable" in the
description of parameters in the converter List Manual (C1,
C2, U, T).
0x6C Parameter %s [%s]: Unknown unit.
0x6D Parameter %s [%s]: Write access only
in the commissioning state, encoder
(p0010 = 4).
0x6E Parameter %s [%s]: Write access only
in the commissioning state, motor
(p0010 = 3).
Communication
A.1 Communication