Network Configurations
© Siemens AG 2002 All Rights Reserved 6NH7811-0AA22
MD2 Modem (07/2002) 5-17
5.1.6 Star Network via an External Multiple Transformer,
2-wire Half-duplex
Overview
Fig. 5-6 shows a configuration for a star network, 2-wire half-duplex.
The MD2 modem on the left represents a 2-wire terminal point to which a multiple
transformer (in this example a 4-way transformer) is connected to connect a star
network consisting of up to four 2-wire dedicated lines. In Fig. 5-6 only two
dedicated lines are shown: the first 2-wire dedicated line is a multidrop line, the
second 2-wire dedicated line is a point-to-point connection.
The MD2 on the right is a 2-wire tapping point, the MD2 modem in the middle is a
2-wire terminal point. All three modems are set to the "Normal" operating mode.
All available baud rates and character recognition methods can be used in this
configuration. However, the 4-way transformer 6NH9812-4GA shown in Fig. 5-6 is
only suitable for 1200 or 2400 bps.
Fig. 5-6 Network configuration: star network via an external multiple transformer, 2-wire half-duplex
4-way transformer
6NH9812-4GA
Note: only suitable
for 1200 or 2400 bps
LTOP2
LTOP2
LTOP1
LTOP2
overvoltage
protection
6NH9821-0BC12
2-wire
dedicated line
DTE
TIM3V/4
MD2
RS232
MD2
RS232
Cable
6NH7700-2AR60
DTE
TIM3V/4
LTOP2
overvoltage
protection
6NH9821-0BC12
DTE
TIM3V/4
MD2
RS232
Cable
6NH7700-2AR60
LTOP1
overvoltage
protection
6NH9821-0BC11
4 x 2-wire-
dedicated
line
1. 2.
3. 4.
Cable
6NH7700-2AR60
Connection to
4-way transformer
requires adaptation
see Table 5-13
600
4 x 600
LTOP2
Terminal point
Terminal point Tapping point
To more
stations