Network Configurations
6NH7811-0AA22 © Siemens AG 2002 All Rights Reserved
5-24 MD2 Modem (07/2002)
5.1.8 Repeater, 4-wire Full-duplex
Overview
Fig. 5-8 shows a configuration for a multidrop line with an intermediate 4-wire
repeater, 4-wire full-duplex and. The MD2 modem on the left represents a 4-wire
terminal point, the MD2 modem on the right is a 4-wire tapping point. Both modems
are set to the "Normal" operating mode. Both MD2 modems in the middle form a 4-
wire repeater and are set to the "Repeater" operating mode.
All available baud rates and character recognition methods can be used in this
configuration.
Note that the DIL switch settings for the modems are different due to their location
in the multidrop line: one is a 4-wire terminal point (see Table 5-16), an other one is
a 4-wire tapping point (see Table 5-17) and two are 4-wire repeaters (see Table 5-
18). The two repeater modems have the same DIL switch settings.
Fig. 5-8 Network configuration: repeater, 4-wire full-duplex
LTOP2
4-wire
dedicated line
DTE
TIM3V/4
MD2
RS232
Cable
6NH7700-2AR60
LTOP2
LTOP2
overvoltage
protection
6NH9821-0BC12
MD2
RS232
LTOP2
DTE
TIM3V/4
Cable
6NH7700-2AR60
4-wire
dedicated line
MD2
RS232
MD2
RS232
Cable 6NH7701-1CB
Cable
6NH7700-2AR60
Cable
6NH7700-2AR60
LTOP2
LTOP2
LTOP2
overvoltage
protection
6NH9821-0BC12
Terminal point Repeater
Tapping
point
Repeater
Repeater