Instructions for Operation with SINAUT ST1
6NH7811-0AA22 © Siemens AG 2002 All Rights Reserved
3-6 MD2 Modem (07/2002)
3.2.2 Configuration Required for TIM11 and TIM011B
If the MD2 modem is connected to the TIM11 or TIM011B, it is necessary to enter
the parameters for the TIM module listed below in the SINAUT ST1 startup
program.
Table 3-7 Configuration Required for TIM11 and TIM011B
Basic Parameters for TIM11 or TIM011BOperating
Mode
of the MD2
Baud rate on the
MD2
MTYP BAUD DUPL SINT SZEI
1200 bps
1 2 3 4
OFF
ON
5
1 1200
1
)
0 0
2400 bps
1 2 3 4
OFF
ON
5
1 2400
1
)
0 0
1) Both half-duplex (DUPL = 0) and full-duplex operating mode (DUPL = 1) can be set.
3.2.3 Avoiding Problems When Exchanging Modems
Note the following points when using the MD2 to replace a defective SINAUT ST1
dedicated line modem:
Set the dedicated line properties, operating mode and the character
recognition on both DIL switches before beginning operation.
Use the cable supplied with the MD2 for connecting the MD2 to the LTOP.
If the MD2 is used in a network together with an MD124 at baud rate 2400 bps
and the MD124 is hardware version 3, the MD124 has to be set to baud rate
2400VF.