EasyManua.ls Logo

Siemens SINAUT ST7 - Page 155

Siemens SINAUT ST7
161 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
6NH7811-0AA22 © Siemens AG 2002 All Rights Reserved
6-6 MD2 Modem (07/2002)
Maximum Range (km)
Table 6-3 Maximum range in relation to the transmission speed with 4dB level reserve.
Standard values for non-coil-loaded telecommunication lines of type
2 x 2 x A J-Y(St)Y (A = core diameter in mm).
Maximum range (km)
Send level –6 dB
*)
Send level 0 dB
*)
Transmission
speed (bps)
with LTOP
without
LTOP
with LTOP
without
LTOP
Core diameter 0.6 mm
1200 21.4 – NTP x 0.8 22 – NTP x 0.3 25.4 – NTP x 0.8 26 – NTP x 0.3
2400 17.4 – NTP x 0.6 17.8 – NTP x 0.2 20.6 – NTP x 0.6 21 – NTP x 0.2
9600 / 19200 6.7 – NTP x 1.0 7.6 – NTP x 0.1 8.1 – NTP x 1.0 9 – NTP x 0.1
Core diameter 0.8 mm
1200 28 – NTP x 1.1 28.7 – NTP x 0.4 33.2 – NTP x 1.1 33.9 – NTP x 0.4
2400 23 – NTP x 0.8 23.5 – NTP x 0.2 27.2 – NTP x 0.8 27.8 – NTP x 0.2
9600 / 19200 9.0 – NTP x 1.4 10.3 – NTP x 0.1 10.9 – NTP x 1.4 12.1 – NTP x 0.1
Core diameter 0.9 mm
1200 35.7 – NTP x 1.4 36.6 – NTP x 0.5 42.4 – NTP x 1.4 43.3 – NTP x 0.5
2400 29.2 – NTP x 1.0 30 – NTP x 0.2 34.7 – NTP x 1.0 35.4 – NTP x 0.2
9600 / 19200 11.1 – NTP x 1.7 12.6 – NTP x 0.1 13.4 – NTP x 1.7 15 – NTP x 0.1
Core diameter 1.2 mm
1200 49.5 – NTP x 1.9 50.7 – NTP x 0.7 58.7 – NTP x 1.9 60 – NTP x 0.7
2400 42.9 – NTP x 1.4 44 – NTP x 0.3 50.9 – NTP x 1.4 52 – NTP x 0.3
9600 / 19200 16.1 – NTP x 2.4 18.3 – NTP x 0.2 19.4 – NTP x 2.4 21.6 – NTP x 0.2
Core diameter 1.4 mm
1200 58.5– NTP x 2.2 60 – NTP x 0.8 69.4 – NTP x 2.2 70.9 – NTP x 0.8
2400 53.6 – NTP x 1.7 55 – NTP x 0.4 63.6 – NTP x 1.7 65 – NTP x 0.4
9600 / 19200 19.3 – NTP x 2.9 22 – NTP x 0.2 23.3 – NTP x 2.9 26 – NTP x 0.2
NTP = number of tapping points
*) not permitted on telecom leased lines. Set send level to –9 dB.