Detailed description
2.12 Block descriptions
Power Line Basic PLC Program (P3)
2-140 Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0
Parameterization:
Signal Type Value range Meaning
PIService ANY PI. TMRASS Reset active status
Unit INT 1 to 10 TO area
Reset monitoring values (TRESMO)
This PI service resets the monitoring values of the designated edges of the designated tools
to their setpoint (initial) values.
This only relates to tools with active monitoring.
Compare this with the RESETMON NC command.
Parameterization:
Signal Type Value range Meaning
PIService ANY PI. TRESMO Reset monitoring values
Unit INT 1 to 10 TO area
WVar1 WORD -max ..max Tool Number
0: Applies to all tools
>0: Applies only to this tool
<0: Applies to all sister tools of the specified T No.
WVar2 WORD 0 ... max. D number
>0: Monitoring of specified edge of specified tools is
reset.
0: Monitoring of all edges of specified tools is reset.
WVar3 WORD 0 ...15 Monitoring types
Type of monitoring to be reset.
This parameter is binary-coded.
1: Tool-life monitoring is reset.
2: Count monitoring is reset.
4: Wear monitoring is reset.
8: Total-offset monitoring is reset.
Combinations of monitoring types can be reset by adding
the values above.
0: All active tool-monitoring functions ($TC_TP9) are
reset.