8.2 DMP compact module 16O (6FC5111-0CA02-0AA2)
8-100
Copyright © Siemens AG 2006
SINUMERIK 810D Equipment Manual Configuration CCU (PHC) – 03/2006 Edition
Table 8-3 Technical data of DMP compact module 16O
Output load for signal “1” (rated value)
Ohmic load 500 mA
Lamp load 5 W
Inductive load 500 mA
Short-circuit protection Yes
Power loss at 30 V Max. 3.8 W
Operating frequency for
Ohmic load 100 Hz
Lamps 11 Hz
Inductive load (for rated
current, higher values are
permissible for lower cur-
rents)
2 Hz
Total load capability at 55
C (relative to the total rated
current of all outputs)
50 %
Delay time for tp
LH
tp
LH
= max. 0.5 ms
Delay time for tp
HL
tp
HL
= max. 0.5 ms
Length for cables Max. 50 m
Weight about 160 g
!
Important
As of version C, a new output driver is used for the DMP compact module 16A.
The following behavior is to be observed:
In the event of a fault triggered by overcurrent or short-circuit, the outputs
automatically reconnect after the fault has been rectified. (previously: latching
disable until the output is reactivated by the PLC user program).
If one output is short-circuited, the three other outputs of the same half-byte can
also be disabled. In normal operation with currents < 0.7 A, there is no mutual
influence.
8 outputs each are powered by a power supply. For each group of 8 outputs
(2 x outputs 0 ... 7), the total of the output currents must not be greater than 2 A.
(This corresponds to a coincidence factor of 50 % if each output is under full
load). All 16 outputs can be loaded simultaneously with 0.25 A for example.
!
Important
If inductive loads are used, switching voltage peaks must be limited by external
free-wheeling diodes or RC connections.