8.3 DMP compact module 8O (6FC5111-0CA03-0AA2)
8-102
Copyright © Siemens AG 2006
SINUMERIK 810D Equipment Manual Configuration CCU (PHC) – 03/2006 Edition
Table 8-4 Technical data of DMP compact module 8O
Number of outputs
8 digital outputs
Galvanic isolation Yes
Power supply V
LOAD
– Rated value 24 V DC
– Perm. range 20.4 V to 28.8 V
– Ripple 3.6 Vpp
Signal level of the outputs (typically)
– For signal “0” Open
– For signal “1” V
load
–80 mV
Output load for signal “1” (rated value)
– Ohmic load 2000 mA
– Lamp load 25 W
– Inductive load 2000 mA
Short-circuit protection Yes
Power loss at 30 V Max. 3.1 W
Operating frequency for – Ohmic load 100 Hz
– Lamps 11 Hz
– Inductive load (for rated
current, higher values are
permissible for lower cur-
rents)
2 Hz
Total load capability at 55
C (relative to the total rated
current of all outputs)
50 %
Delay time for tp
LH
tp
LH
= max. 0.5 ms
Delay time for tp
HL
tp
HL
= max. 0.5 ms
Length for cables max. 50 m
Weight about 145 g
!
Important
As of product version B, a new output driver is used for the DMP compact
module 8O. It behaves as follows:
In the event of a fault triggered by overcurrent or short-circuit, the outputs
automatically reconnect after the fault has been rectified.
4 outputs each are powered by a power supply. For each group of 4 outputs
(outputs 0 to 3 and 4 to 7), the total of the output currents must not be greater
than 4 A. (This corresponds to a coincidence factor of 50 % if each output is
under full load). All 8 outputs can be loaded simultaneously with 1 A for
example.
!
Important
If inductive loads are used, switching voltage peaks must be limited by external
free-wheeling diodes or RC connections.
8 DMP Com