Project Planning Manual SIPART DR20
S 1 = 0
S 15 = 1
S 16 = 0
S 17 = 1
S 19 = 1
100
0
w
1
w
2
T
w
t
w (%)
w
1
Si = 1 Si = 0
Fig. 11/2 Setpoint response according to example 2
Example 3: Two-setpoint mode with a synchronization controller without local / remote
switchover:
1. One variable setpoint w1 = c2 ∗ wE + c1
2. The setpoint w2 = c1 defined by parameterization and not affected by
the front controls
Both setpoints are thus linked by the fixed component c1; the switch-over
from w1 to w2 takes place simply by external switching off of w2. A setpoint
ramp Tw > 0 is provided.
S1 = 6
100
0
w
1
w
2
w
E
= 0
t
w (%)
w
1
= w
E
* c2 + c1
w
2
= c1 (parameter)
w
E
T
w
Fig. 11/3 Setpoint response according to example 3
104