EasyManuals Logo

Siemens SIPART DR20 User Manual

Siemens SIPART DR20
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Project Planning Manual SIPART DR20
S1 = 5 Follow-up controller with local/remote switch over (Fig. 3/13)
This controller type is suitable for SPC mode and operation with two or three setpoints (wi, wE,
wS). The remote setpoint can be entered either via an analog input as a variable wE or via the
serial interface as wES.
In SPC mode the setpoint is tracked by a higher-level computer (control system). SPC mode is
present if the device is switched to remote setpoint and the signal CB is present simultaneously:
NOT(H) AND CB AND NOT(I) = RC = 1
A status LED does not light up in this (normal) case. The green LED 14 flashes with a duty cycle of
0.5 if the computer fails (CB = 1 Æ 0) and further control is made either with the local setpoint wi
which tracked the last valid setpoint (S18 = 0) or with the parameterized safety setpoint wS
(x-tracking is also possible if automatic mode is not present = /A). If the setpoint selector 13 is
activated (INT = 1), the green LED becomes steady and the setpoint can be adjusted manually.
The green LED flashes with a duty factor of 0.9 if the CB signal reappears during local mode but
this mode is retained until a remote setpoint is again selected using pushbutton 13.
The following table (Fig. 3/10) provides a summary of signals and effective setpoints depending on
control signals and the configuring switches S17, S18 and S19.
Signals
Control commands
front and digital
inputs **)
Front
LED ***)
Digital
output
Effec-
tive
output
Effective setpoint
S19=0
H+N+Si+BL CB INT INT H /RB /RC Y S17=0
S18=0
=1
=0
=0
=1
=1
=1
Explanations
Computer
failure
0 1 0 0 0 0 0 yA(n) wE(n) *) wE(n) *) wE(n) *) wE(n) *) Automatic mode, SPC-mode
0 0 0 0,5 0 0 1 yA(n) wi(n) wi(n) wS wS Automatic mode, computer
switched OFF, controller at SPC
standby
0 1 1 0,9 0 1 1 yA(n) wi(n) wi(n) wi(n) wi(n) Automatic mode, computer at
standby, controller not at SPC
standby
0 0 1 1 0 1 1 yA(n) wi(n) wi(n) wi(n) wi(n) Automatic mode, computer
switched OFF, controller not at
SPC standby
1 1 0 0
>0
1 1 yH or wE(n) *) x wE(n) *) x
1 0 0 0,5
>0
1 1 yE or wi(n) x wS x
1 1 1 0,9
>0
1 1 yS or wi(n) x wi(n) x
1 0 1 1
>0
1 1 yBL wi(n) x wi(n) x
Manual, tracking, safety mode
or blocking of output,
controller not at SPC standby
Fig. 3/10 Follow-up controller with local/remote switchover,
SPC controller with tracking of local setpoint (S19 = 0)
*) Sources for wE are wEA (remote analog value, e.g. from master controller) or wES
(remote value via serial interface). Only wES can be tracked, of course, not wEA
(see Fig. 3/13).
**) When using the digital input BE, only one of the control variables CB, Si, BL or N is possible
as defined by S15. The priority is Si before BL before N (DDC) when applied via the
serial interface.
***) The data on "Signals front LED" (e.g. 0.5) refer to the flashing frequency (see 3.2.6).
(n) The variable is made to track the last value effective before switchover.
NOT(RC) = NOT{NOT(INT) AND CB AND NOT(H)} NOT(RB) = INT OR H
34

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART DR20 and is the answer not in the manual?

Siemens SIPART DR20 Specifications

General IconGeneral
BrandSiemens
ModelSIPART DR20
CategoryController
LanguageEnglish

Related product manuals