SIPART DR20 Project Planning Manual
Serial interface (6DR2803-8A)
Communication signals
Transferable data
Communications procedure
Character format
Hamming distance d
Transmission speed
Transmission
Addressable stations
Data traffic watch-dog
Transmit output Txd
Signal level "0"
Point-to-point
Bus
Signal level "1"
Point-to-point
Bus
Receive input Rxd
Signal level "0"
Signal level "1" *)
Electrical isolation
V.24 / V.28 signals to CCITT - V.24
Operational status, process variables,
parameters and configuring switches
to DIN 66258 A or B
10 bits (start bit, ASCII character with 7 bit,
parity bit and stop bit)
2 or 4
300 to 9600 bit/s
Asynchronous, half-duplex
Full-duplex for NAK
32
1 to 25 s or none
V.28
U
A
= + 5 to + 12 V
I
A
max. 1.67 mA } short-circuit-
I
A
max. 15 mA } proof
U
A
= - 5 to - 12 V
I
A
max. 1.67 mA
UA 0 V
V.28
U
A
= 0 to + 35 V
I
E
= (U
E
- 0.7 V) / 6.8 k
U
A
= - 3 to - 35 V
I
E
= (U
E
+ 1.5 V) / 6.8 k
Txd: without (referred to M (Ground))
Rxd: by opto isolator
Recommended length
Cable capacitance and length at 9600 bit/s
Cable
capacitance
Unscreened
ribbon cable
Screened round
cable
V.28 point-to-point
2.5 nF
50 m 10 m
SIPART Bus with bus driver **)
25 nF
500 m 100 m
TTY point-to-point with bus driver **)
75 nF
1500 m 300 m
*) Signal level "1" is the rest position
**) Bus driver C73451-A347-B202
An external power supply (± 24 V, 100 mA) is required for the bus driver
69