Operation
118
SIPAR T PS2 Manual
A5E00074631--06
Monitoring of the upper temperature limit
The current temperature in the positioner housing is measured by a
sensor on the electronic circuit board. This parameter is for the
three-level monitoring of the upper temperature limit.
Temperature unit
The temperature unit can be switched over by pressing the Greater
Than or Smaller Than button between °C and °F. Another way of
switching over is the H1.TUNIT parameter for monitoring the lower
temperature limit. The selected unit applies to all temperature-related
parameters.
Threshold 1
First threshold for monitoring the upper temperature limit. The factory
setting is 75.0°C. If the temperature exceeds the set value, the thres-
hold 1 error message is triggered.
Threshold 2
Second threshold for monitoring the upper temperature limit. The
factory setting is 80.0°C. If the temperature exceeds the set value,
the threshold 2 error message is triggered.
Threshold 3
Third threshold for monitoring the upper temperature limit. The factory
setting is 90.0°C. If the temperature exceeds the set value, the thres-
hold 3 error message is triggered.
J. TMAX
J1.TUNIT
J2.LEVL1
J3.LEVL2
J4.LEVL3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 6DR50xx and is the answer not in the manual?

Siemens SIPART PS2 6DR50xx Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 6DR50xx
CategoryValve Positioners
LanguageEnglish

Related product manuals