Technical Data
151
SIPAR T PS2 Manual
A5E00074631--06
Technical specifications
Option modules Without Ex protection
(EEx d also)
With Ex protection EEx ia/ib With Ex protection EEx n
Ex protection to EN 50014, EN 50020 and
EN 50021
II 2G EEx ia/ib II C T4/T5/T6 II 3G EEx nA L [L] II C T6
Mounting location Zone 1 Zone 2
Permissible ambient temperature for opera-
tion
(For devices with Ex protection: Only in con-
junction with the basic device 6DR5... -.E....
Only T4 is permissible when using I
y
module)
-30 ... +80 °C (-22 ... +176 °F) T4: -30 ... +80 °C (-22 ... +176 °F)
1)
T5: -30 ... +65 °C (-22 ... +149 °F)
1)
T6: -30 ... +50 °C (-22 ... +122 °F)
1)
Alarm module 6DR4004-8A (without Ex protec-
tion)
6DR4004-6A (with Ex protection) 6DR4004-6A (with Ex protection)
Binary alarm outputs A1, A2 and alarm output
Signal status High (not responded)
Signal status Low* (responded)
(* Low is also the status when the basic
device is faulty or has not electric power sup-
ply)
Active, R = 1 k, +3/-1%*
Disabled, I
R
< 60 µA
2.1 mA
1.2 mA
2.1 mA
1.2 mA
(* When used in the flameproof
casing the current consumption
is limited to 10 mA per output.)
(Switching threshold with sup-
ply to EN 60947-5-6: U
H
= 8.2 V,
R
i
= 1k)
(Switching threshold with sup-
ply to EN 60947-5-6: U
H
= 8.2 V,
R
i
= 1k)
Internal capacitance C
i
5.2 nF
Internal inductance L
i
Negligible
Power supply U
H
35 V
Connection to power circuits with intrinsically safe switching
amplifier EN 60947-5-6
U
o
15.5 V DC
I
k
25 mA, P 64 mW
U
i
15.5 V DC
Binary input BE2
Electrically connected to the basic device
- Signal status 0 Floating contact, open Floating contact, open Floating contact, open
- Signal status 1 Floating contact, closed Floating contact, closed Floating contact, closed
- Contact load 3 V, 5 µA3 V, 5 µA3 V, 5 µA
Electrically isolated from the basic device
- Signal status 0 4.5 V or open 4.5 V or open 4.5 V or open
- Signal status 1 13 V 13 V 13 V
- Natural resistance 25 kΩ≥25 kΩ≥25 k
Static destruction limit ± 35 V
Internal inductance and capacitance Negligible
Connection to power circuits Intrinsically safe U
i
25.2 V U
i
25.2 V DC
Electrical isolation The 3 outputs, the input BE2 and the basic device are electrically isolated from each other
Test voltage 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s
SIA module (not for EEx d version) 6DR4004-8G (without Ex protec-
tion)
6DR4004-6G (with Ex protec-
tion)
6DR4004-6G (with Ex protec-
tion)
Limit transmitter with slot-type initiators and
alarm output
2-wire connection
Ex protection Without II 2 G EEx ia/ib IIC T6 II 3 G EEx nA L [L] IIC T6
Connection 2-wire system to EN 60947-5-6 (NAMUR), for switching amplifier to be connected on load side
2 slot-type initiators Type SJ2-SN Type SJ2-SN Type SJ2-SN
Function NC (normally closed) NC (normally closed) NC (normally closed)
Connection to power circuits with nominal voltage 8 V
Current consumption:
3 mA (limit value not
responded)
1 mA (limit value
responded)
Intrinsically safe switching
amplifier EN 60947-5-6
U
i
15.5 V DC
I
i
25 mA, P
i
64 mW
U
i
15.5 V DC
P
i
64 mW
Internal capacitance 41 nF
Internal inductance 100 mH
Electrical isolation The 3 outputs are electrically isolated from the basic device
Test voltage 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s
Alarm output See Alarm module See Alarm module See Alarm module
1)
Only in conjunction with the basic device 6DR5...-E..... With Iy module only T4 permitted.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 6DR50xx and is the answer not in the manual?

Siemens SIPART PS2 6DR50xx Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 6DR50xx
CategoryValve Positioners
LanguageEnglish

Related product manuals